產品詳情
保護電路
| IEC 類別 | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| 額定電壓 UN | 24 V DC |
| 最大持續工作電壓UC | 30 V DC |
| 21 V AC | |
| 額定電流 | 1000 mA (40 °C) |
| UC時,有效工作電流IC | ≤ 1 mA (在信號回路內) |
| 殘流IPE | ≤ 2 μA (每個信號回路) |
| 標稱放電電流In (8/20) μs(線芯-線芯) | 10 kA |
| 標稱放電電流In (8/20) μs(線芯-地) | 10 kA |
| 脈沖放電電流Iimp (10/350) μs(線芯-地) | 2.5 kA |
| 總放電電流Itotal (8/20) μs | 20 kA |
| 電壓保護水平Up(線芯-線芯) | ≤ 80 V (C1 - 1 kV/500 A) |
| ≤ 130 V (C2 - 10 kV / 5 kA) | |
| ≤ 150 V (C2 - 10 kA) | |
| ≤ 55 V (C3 - 25 A) | |
| ≤ 60 V (C3 - 100 A) | |
| 電壓保護水平Up(線芯-地) | ≤ 600 V (C1 - 1 kV/500 A) |
| ≤ 750 V (C2 - 10 kV / 5 kA) | |
| ≤ 800 V (C2 - 10 kA) | |
| ≤ 700 V (C3 - 25 A) | |
| ≤ 800 V (C3 - 100 A) | |
| 電壓防護等級Up靜態(線芯-線芯) | ≤ 65 V (C1 - 1 kV/500 A) |
| ≤ 65 V (C2 - 10 kA) | |
| 響應時間tA(線芯-線芯) | ≤ 1 ns |
| 響應時間tA(線芯-地) | ≤ 100 ns |
| 輸入衰減aE,對稱 | 典型值 0.3 dB (≤ 270 kHz/150 Ω) |
| 截止頻率fg(3dB),150 Ω 對稱系統 | 典型值 1.1 MHz |
| 電容(線芯-線芯) | 典型值 2 nF |
| 每條路徑的電阻 | 1.2 Ω ±5 % |
| 電涌保護故障報警 | 視覺,多階段 |
| 需要的最大備用保險絲 | 1 A (FF) |
| 電涌電流電阻(導線-導線) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C2 - 10 kA | |
| C3 - 100 A | |
| 電涌電流電阻(導線-接地) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C2 - 10 kA | |
| C3 - 100 A | |
| D1 - 2.5 kA | |
| 脈沖復位時間(導線-導線) | ≤ 4000 ms |
| 脈沖復位時間(導線-接地) | ≤ 2600 ms |
接線數據
| 連接方式 | 螺釘連接 |
|---|---|
| 螺紋 | M3 |
| 緊固力矩 | 0.5 Nm |
| 剝線長度 | 8 mm |
| 柔性導線橫截面 | 0.2 mm2 ... 2.5 mm2 |
| 硬導線橫截面 | 0.2 mm2 ... 4 mm2 |
| 可連接導向橫截面 AWG | 24 ... 12 |



